REHAU INTELLIGENT FS/FC HEATING/COOLING CONTROLSTECHNICAL & INSTALLATION MANUALBuilding SolutionsAutomotiveIndustrywww.rehau.co.uk

Page 2 - REHAU INTELLIGENT FLOOR

11Please note fixed flow temperature regulation is not suitable for use with FS and FC controllersCP4 Port MxingHLSTSManifold Flow HeaderManifold Retu

Page 3

12PRINCIPLES OF UNDERFLOOR HEATING/COOLINGZONE CONTROL1.01.4UFH - ManifoldACACACHLSIVIVUFH - ReturnUFH - FlowRS - Room SensorHS - Humidity Sensor (onl

Page 4

13 PRINCIPLES OF UNDERFLOOR HEATING/COOLINGSET-BACK MODE 1 . 01.51.5.1 Heating A fl oor heating system switches into set-back mode instead of switching

Page 5

14FLOW TEMPERATURE CONTROLSAFETY ADVICE2.02.1Authorised specialistsInstallation, commissioning, maintenance and repairs of all electrical control comp

Page 6

15* 4 valves are required to provide safety protection to prevent any cross flow within the 2 systems should the boiler and the chiller operating at t

Page 7 - PRINCIPLE OF UFH

16 FLOW TEMPERATURE CONTROLFOUR PORT MOTORISED MIXING VALVE (MV) HEATING/COOLING 2 . 02.32.3.1 Working Principle The high or low temperature main syst

Page 8 - PRINCIPLE OF UFC

17 Required Components QtySupplied by REHAUMixing Valve Actuator 1x YesMale iron to copper adapters 4x NoCirculating Pump (CP) 1x NoIsolating Valve (

Page 9

18FLOW TEMPERATURE CONTROLFOUR PORT MOTORISED MIXING VALVE (MV) HEATING/COOLING2.02.3H. ANTI ROTATION STUDJ. VALVE SPINDLEK. VALVE PLATEL. VALVE BODYG

Page 10 - Cooling Module

19FLOW TEMPERATURE CONTROLVARIABLE TEMPERATURE (VT) MIXING OPTION FOR HEATING/COOLING2.02.4Technical Data Mixing Valve (4 Port)For up to 12kW:Dimensio

Page 11 - UFH/C Control centre

20 FLOW TEMPERATURE CONTROLFLOW TEMPERATURE SAFETY OPTIONS 2 . 02.52.5.1 Dew Point ControlThe dew point control of the system is performed by the Heat

Page 12 - SET-BACK MODE

3REHAU INTELLIGENT FLOOR HEATING/COOLING CONTROLSINDEX1.0 . . . . . . Principles of Underfloor Heating/Cooling . . . . . . . . . . .

Page 13 - FLOW TEMPERATURE CONTROL

21 FLOW TEMPERATURE CONTROLZONE VALVES (ZV) 2 . 02.62.6.1 Working Principle (HEATING) The 2-port zone valve (ZV) has a dual function:- To separate th

Page 14

22If fitted in a confined space, sufficient ventilation must be available to keep the valve within its ambient temperature range. Also access must be pro

Page 15 - FLOW TEMPERATURE CONTROL

232.6.3 Working Principle (HEATING & COOLING) In a Heating/Cooling system the zone valves are a safety mechanism. The system is designed not to op

Page 16

24 REHAU INTELLIGENT FH / C ZONE CONTROL SYSTEMCOMPONENTS OVERVIEW 3 . 03.13.1.1 Components Overview HeatingComponent Article numberREHAU FS Controlle

Page 17

25Component Article numberREHAU OC Module, Outside Air Temperature Sensor225117-001(5V)The module is only required if the REHAU FS variable temperatur

Page 18

26Component Article numberREHAU FC Controller202236-001(24V)Variable TemperatureThe REHAU FC controller is suitable for connecting up to 8 zones of mu

Page 19

27Component Article numberREHAU RC, Wireless Receiver202244-001(5V)The wireless receiver is required to receive signals from wireless sensors/controll

Page 20

28REHAU INTELLIGENT FH / C ZONE CONTROL SYSTEMWORKING PRINCIPLE3.0 3.2The sophisticated electronic control system was designed specifically for under

Page 21

29Optimum start controlREHAU CT2 Programmable Room Sensor, Radiator and Two stage controllers have an advanced time clock that learns how quickly a bu

Page 22 - FC Controller (Main Control)

30REHAU INTELLIGENT FH / C ZONE CONTROL SYSTEMWORKING PRINCIPLE3.0 3.23.2.1 Weather CompensationWeather compensation using Intelligent controlsWeathe

Page 23 - C ZONE CONTROL SYSTEM

4REHAU INTELLIGENT FLOOR HEATING/COOLING CONTROLSINDEX4.0 . . . . . . Control System First Fix . . . . . . . . . . . . . . . .

Page 24

31Note Maximum manifold Size = 12-Port3.2.2 Required Components for Zone ControlThis table should help you identifying which components you need depen

Page 25

32CONTROL SYSTEM FIRST FIXCABLES REQUIREMENTS4.0 4.1All REHAU control systems must be installed:- By a competent person.- In accordance with all loc

Page 26

334.2.1 Location of Room, Humidity Sensor and Air SensorThe requirement for the correct positioning room sensors cannot be overstated. Care must be ta

Page 27 - REHAU INTELLIGENT FH /

34CONTROL SYSTEM FIRST FIXWIRELESS SENSORS/CONTROLLERS SET UP/RADIO FREQUENCY (RF) 4 . 04.3REHAU wireless sensors can be used in conjunction with wire

Page 28 - Potential energy savings

354.3.2 Technical Data Supply Voltage24 V from MasterDistance to masterMax 3 mEnclosureIP 21Ambient temperature range0 to 40°CCommunication Frequency8

Page 29

36CONTROL SYSTEM SECOND FIXREHAU FS/FC CONTROL UNITS 5 . 05.1The REHAU FS and FC control unit can operate 8 zones. The REHAU FC zones can be heating o

Page 30

375.2.3 Boiler ConnectionThe REHAU FS/FC control unit has a volt free relay, which may be used to switch a boiler or to open a motorised valve.Connect

Page 31 - CONTROL SYSTEM FIRST FIX

38CONTROL SYSTEM SECOND FIXMAINS VOLTAGE (230V) ELECTRICAL CONNECTION TO THE FS/FC CONTROLLER5.0 5.25.2.4 X-Relay OutputBoth FS and FC controllers ha

Page 32

395.2.6 Connecting the Heating/Cooling Zone ValvesThe zone valves REHAU Art No. 230462 (22mm) and Art No. 230472 (28mm) must be used on the system and

Page 33

40CONTROL SYSTEM SECOND FIXMAINS VOLTAGE (230V) ELECTRICAL CONNECTION TO THE FS/FC CONTROLLER5.0 5.2Pump control with REHAU Add On ModulesThe REHAU A

Page 34 - Receiver (RC)

56.0 . . . . . . System Start Up and Operating Instructions for Heating & Cooling . . . . . . . . 466.1 . . . . . . Mixing V

Page 35 - CONTROL SYSTEM SECOND FIX

415.3.1 Connecting the Add On, Extension ModuleThe addition of REHAU Add On extension module will increase the zoning potential from 8 to 14 zones. Th

Page 36

425.3.3 Connecting Thermal Actuators (TH 1 – TH 8)Maximum 14 x 24 Volt actuators per controller. Ensure that the actuators are connected to the correc

Page 37

435.3.5 Connecting 4-Port Mixing Valve Actuator To enable the system to be weather compensated the supply pipework to the manifolds must be fitted with

Page 38

44CONTROL SYSTEM SECOND FIXROOM SENSORS INTERNAL CONNECTIONS5.0 5.4++To ControllerRemote air sensorTM Room SensorUnlike the REHAU TD floor sensor the

Page 39

45Mode selection switch Temperature dial Mode selection switch Temperature dial Jumper in position for max. floor surface temperatureJumper in positio

Page 40

46SYSTEM START UP AND OPERATING INSTRUCTIONS FOR HEATING & COOLING MIXING VALVE ACTUATOR6.0 6.140. Variable temperature wiringWhen all electrical

Page 41

47SYSTEM START UP AND OPERATING INSTRUCTIONS FOR HEATING & COOLING SETTING THE HEATED/COOLED ZONES (CHANNEL NUMBERS) 6.0 6.2A) DisplayB) Down Adju

Page 42 - FS/FC Master Controller

48SYSTEM START UP AND OPERATING INSTRUCTIONS FOR HEATING & COOLING SETTING UP THE REHAU FS/FC CONTROLLER (HEATING)6.0 6.3The FS/FC controller come

Page 43

496.3.1 Adjusting the Pre-Set Default Temperatures in the REHAU FS/FC ControllerFunction Factory Setting To modifyDay Temperature ( ) 21°C 1. Loc

Page 44 - TD ROOM SENSOR

50Function Factory Setting To modifySetting the Winter Water Temperature 45°C 1. Locate the winter water temperature symbol ( ) by pressing the

Page 45 - Actuator

6REHAU INTELLIGENT FLOOR HEATING/COOLING CONTROLSINDEX11.0 . . . . . . Troubleshooting and Error/Fault Messages . . . . . . . . . . .

Page 46

511. Factory setting2. Example of user settingMAX’ FLOW WATERWinter -3°C (outdoor temperature)= Water temperature > 45°CSummer 25°C (outdoor temper

Page 47

52SYSTEM START UP AND OPERATING INSTRUCTIONS FOR HEATING & COOLING SETTING UP THE FC CONTROLLER (COOLING)6.0 6.5Function Description Factory Setti

Page 48

53Function Description Factory Setting To modify(G) System Mode Selection This option will allow the function of the controller to be set the control

Page 49

546.5.1 Setting up Dehumidifier on the Master ConnectionSYSTEM START UP AND OPERATING INSTRUCTIONS FOR HEATING & COOLING SETTING UP THE FC CONTROLL

Page 50 - 2. Example of user setting

55COMMISSIONING7.0The defi nition of commissioning, according to CIBSE (Chartered Institution of Building Services Engineers) is the advancement of an

Page 51

567.3 Initial System Start Up for Cooling Systems It is important that the initial heating system start up procedure (section 7.2, see page 55) is car

Page 52

57 8 . 08.1CT SET UP GUIDEPROGRAMMABLE ROOM SENSOR, DOMESTIC HOT WATER,RADIATOR AND TWO STAGE CONTROLLERCT2 Programmable Room Sensor, CT2 / R Radiat

Page 53 - FC Master Controller

581. The time will have to be set as soon as the CT2 Programmable Room Sensor is switched on for the first time, the hour digits start to flash.1.1

Page 54 - COMMISSIONING7.0

591.6 Repeat for each channel as desired. To leave this menu, either go through all 14 channels and press ESC (below) or don’t press any butto

Page 55

602.1a Hold the button for 3 seconds. This screen will be displayed. This shows the start time of the first event, DAY, which is the first time

Page 56 - CT SET UP GUIDE

7If a floor heating system is added to an existing heating or hot water system, containing mild steel pipes, a strainer must be fitted straight after th

Page 57

612.6a Days 6 and 7 (Saturday and Sunday) only have 2 events - DAY and NIGHT. This screen shows the start time of day event. Adjust if required as

Page 58

624. Changing event sequence over different days (if required) Hold UP and DOWN buttons to reach sub-menus. Scroll through and press on Pro. The

Page 59

635.2 Select LoLi if minimum floor sensor fitted.5.3 Adjust minimum floor sensor temperature as above.6. To See Current Sensor Info Hold UP and DOW

Page 60

647.1 Press UP and DOWN to scroll through options and to select desired scale. The first is 24 hour clock and temperature in celsius.7.2 24 hour

Page 61

659.2a Use the UP and DOWN arrows to either select ON.9.2b or OFF.Press to confirm, then the next channel will appear.9.3 ‘LEAP’ will start t

Page 62

66DOMESTIC HOT WATER (DHW), RADIATORS AND TWO STAGE CONTROLLERDOMESTIC HOT WATER (DHW)9.0 9.1BoilerCP4 Port Mxing ValveTSManifold Flow HeaderManifold

Page 63

67DOMESTIC HOT WATER (DHW), RADIATORS AND TWO STAGE CONTROLLERRADIATORS9.0 9.2BoilerCP4 Port Mxing ValveTSManifold flow headerManifold return headerZ

Page 64

68DOMESTIC HOT WATER (DHW), RADIATORS AND TWO STAGE CONTROLLERTWO STAGE ROOM TEMPERATURE CONTROLLER9.0 9.3Working PrincipleREHAU CT2/2 provides two s

Page 65 - DOMESTIC HOT WATER (DHW)

69SPECIAL FUNCTIONSNETWORKING MULTIPLE CONTROLLERS10.010.1BoilerCPTSPDBCPPDBIVPV OCCirculating PumpPressure Differential ByepassIsolating ValvePressur

Page 66

70SPECIAL FUNCTIONSDIP SWITCHES10.010.2DIP Switch Function Description DIP switches (located on the master controller)1 Turn on to activate install m

Page 67

8PRINCIPLES OF UNDERFLOOR HEATING/COOLINGPRINCIPLE OF UFHThermal ComfortREHAU underfloor heating system operates on the basis of low surface temperatur

Page 68 - SPECIAL FUNCTIONS

71Dependent upon the control system configuration it is possible to override all the automatic functions of the control system with a single function.T

Page 69

72SPECIAL FUNCTIONSCHECKING CONTROL SYSTEM OPERATION10.010.4System check procedure1. Sensor check:a. Switch on DIP-3 to activate sensor check - power

Page 70

73TROUBLESHOOTING AND ERROR/FAULT MESSAGESTROUBLESHOOTING11.011.1Problem Possible cause & SolutionChannel light is not coming on (When in Server

Page 71

74Problem Possible cause & SolutionMixing valve does not operate correctly (When in install mode)Incorrect connection, see master wiring diagram f

Page 72 - TROUBLESHOOTING

75During normal operation the green power LED will be ON when the Master Controller is energised. The red output Channel LED’s (1 to 8 on the Master C

Page 73

7611.2.2 Flashing Output LED (red):The appropriate output channel LED can flash, indicating that the Room Sensor or Controller on that channel has a fa

Page 74 - ERROR/FAULT MESSAGES

77RESETS 1 2 . 0There are two different reset actions that can be used on the FS Master Controller:Resets To Enable FunctionHard Reset*(used if there

Page 75

78SENSOR FAILURE/VALVE AND PUMP EXERCISE13.0 13.1 Sensor/Controller FailureIf a Room Sensor/Controller is defective or if the communication to the uni

Page 76 - RESETS 1 2 . 0

Wiring Schematic - next generationrehaU FS maSter controller With aDD on moDUleT T+ +CHANNEL 1SUPPLY230VACBOILERB1 B2X-RELAY SEC. PUMP230VACLL NNLINKC

Page 77

www.rehau.co.uk 864.602EN/E&T/06.08Our verbal and written application engineering advice is based upon experience and the best of our knowledge. H

Page 78 - CHANNEL 1

9PRINCIPLES OF UNDERFLOOR HEATING/COOLINGPRINCIPLE OF UFCAdvantages of a Underfloor Cooling System - High level of comfort- Draughts do not occur-

Page 79

10PRINCIPLES OF UNDERFLOOR HEATING/COOLINGFLOW TEMPERATURE CONTROL 1.01.3HeatingA boiler for a conventional combined radiator and domestic hot water s